WhatsApp
Telefon
Instagram

Prysmian PPG-Png(A)-HF 660V – Copper conductor, halogen-free insulated, flame retardant and low smoke power cable

       

Prysmian PPG-Png(A)-HF 660V – Copper conductor, halogen-free insulated, flame retardant and low smoke power cable

0AZN

Prysmian PPG-Png(A)-HF cables are designed for transmission and distribution of electrical energy at a voltage of 0.66 kV. It is suitable for use in public buildings such as school, hospital, stadium, shopping mall, high-rise building and subway.
The cable is a solid copper conductor (Class 1), and the insulation and sheath are halogen-free polymer material. The cable is halogen-free, flame retardant (IEC 60332-3-22), low smoke (IEC 61034-2), UV-resistant and has an operating temperature of up to +70 °C.
Dimensions:

  • 2×1.5 mm² → insulation Ø 2.6 mm, height 5.5 mm, width 8.1 mm, weight 81 kg/km, resistance 12.1 Ω/km, current 21 A

  • 3×1.5 mm² → insulation Ø 2.6 mm, height 5.5 mm, width 10.7 mm, weight 113 kg/km, resistance 12.1 Ω/km, current 21 A

  • 2×2.5 mm² → insulation Ø 3.0 mm, height 5.9 mm, width 8.9 mm, weight 104 kg/km, resistance 7.41 Ω/km, current 27 A

  • 3×2.5 mm² → insulation Ø 3.0 mm, height 5.9 mm, width 11.8 mm, weight 148 kg/km, resistance 7.41 Ω/km, current 27 A

  • 2×4 mm² → insulation Ø 3.7 mm, height 6.5 mm, width 10.1 mm, weight 145 kg/km, resistance 4.61 Ω/km, current 36 A

  • 3×4 mm² → insulation Ø 3.7 mm, height 6.5 mm, width 13.8 mm, weight 209 kg/km, resistance 4.61 Ω/km, current 36 A

  • 2×6 mm² → insulation Ø 4.2 mm, height 7.0 mm, width 11.1 mm, weight 189 kg/km, resistance 3.08 Ω/km, current 46 A

  • 3×6 mm² → insulation Ø 4.2 mm, height 7.0 mm, width 15.3 mm, weight 275 kg/km, resistance 3.08 Ω/km, current 46 A

Standards
GOST 31996, TS 3533-014-50951092-2019, IEC 61034-2:2011, IEC 60754-1:2011, IEC 60332-3-22:2011