This cable is designed for fixed installation in industrial and power transmission systems. XLPE insulation provides high thermal and electrical stability, steel tape armor provides protection against mechanical effects, and low smoke and flame retardant PVC coating reduces the spread of flame and harmful gases in the event of a fire. The cable is suitable for both underground and outdoor use.
Structure of the cable:

  • Conductor - multi-stranded round clipped aluminum wires, IEC 60228, class 2

    • Cross-sectional area for 25–240 mm²

  • Inner screen - extruded semi-conductive polyethylene

  • Insulation – XLPE (cross-linked polyethylene, 2X)

  • Outer semi-conductive layer – semi-conductive polyethylene

  • Separator layer – semiconductor blocking tape

  • Screen – copper wire and copper tape (SE)

    • min for 25–120 mm². 16 mm²

    • min for 150–240 mm². 25 mm²

  • Inner coating – PVC plastic

  • Armour – double steel band

  • External coating – low smoke and non-flammable PVC (Y-LS)

  • Heat tolerance

    • Normal working temperature: +90°C

    • Short-term loading: +130°C

    • Short circuit (5 s): +250°C

    Dimensions
    3×25 mm² – 3×240 mm²