WhatsApp
Telefon
Instagram

(N2XSY-fl) XLPE insulated, flame retardant PVC sheathed copper conductor single core high voltage cable

       

(N2XSY-fl) XLPE insulated, flame retardant PVC sheathed copper conductor single core high voltage cable

0AZN

N2XSY-fl branded cables comply with AZS 418-2010 (TS IEC 60502-2), TSE K 204 standards and are of the same technical class as the RUS KABEL analogue.
These cables are used in industrial areas, cable lines and stationary installation systems. It can be installed on dry land and where level differences are limited. The cable does not spread flames thanks to its anti-flammability polyvinyl chloride (Y-fl) coating and ensures safe operation even when installed in a group.

Construction:

  • Conductor: multi-stranded circular crimped copper, class 2 according to IEC 60228

    • 25–800 mm²: round clamped formal vessel

    • 1000–1600 mm²: multiwire formal vessel with 5 sectors

  • Supervascular screen: Extruded semiconducting polyethylene

  • Insulation: Polyethylene (XLPE)

  • Insulating screen: Extruded semi-conductive polyethylene

  • Separator layer: Blocking semiconductor tape

  • Screen: Copper wires and binding copper tape (S)

  • Separating layer: PET-F tape

  • External coating: Non-flammable polyvinyl chloride (Y-fl)

  • Technical indicators:

    • Operating temperature: +90°C

    • Maximum heating temperature during gas: +1300°C

    • Maximum temperature of vessels during short circuit: +250°C

    • Minimum bending radius: 15×D (D – cable outer diameter)

    • Minimum installation temperature: -15°C

    • Maximum insulation temperature: +90°C

    • Nominal voltage: 6–30 kV

    • Service life: 30 years

    Dimensions
    1×25–1600 mm²